Technical Documentation

Converting mA to Voltage Signals

Amps Ohms Volts Gauge

Converting mA to voltage is common in HVAC when working with pressure transducers. Terminology to keep in mind includes:

  • 1 mA = 0.001 AMP (short for amperes)

  • Amps are referred to as CURRENT

  • Resistor values are in OHMS (Ω is the symbol for ohms)

  • VOLTAGE is the result of passing amps through a resistor

In order to change mA (current) to voltage, you need to pass the current through a resistor.

The formula for voltage is:

E = IR
E stands for volts, I stands for amps, and R stands for resistance

In control circuits, the most common resistor values are 250Ω & 500Ω, although any value can be used depending upon the device.


If your control circuit is using a 250Ω resistor:

mA

Amps x Resistance

Volts

4

0.004 x 250Ω

1

5

0.005 x 250Ω

1.25

6

0.006 x 250Ω

1.5

7

0.007 x 250Ω

1.75

8

0.008 x 250Ω

2.0

9

0.009 x 250Ω

2.25

10

0.010 x 250Ω

2.5

11

0.011 x 250Ω

2.75

12

0.012 x 250Ω

3.0

13

0.013 x 250Ω

3.25

14

0.014 x 250Ω

3.5

15

0.015 x 250Ω

3.75

16

0.016 x 250Ω

4

17

0.017 x 250Ω

4.25

18

0.018 X 250Ω

4.5

19

0.019 x 250Ω

4.75

20

0.020 x 250Ω

5


If your control circuit is using a 500Ω resistor:

mA

Amps x Resistance

Volts

4

0.004 x 500Ω

2

5

0.005 x 500Ω

2.5

6

0.006 x 500Ω

3

7

0.007 x 500Ω

3.5

8

0.008 x 500Ω

4

9

0.009 x 500Ω

4.5

10

0.010 x 500Ω

5

11

0.011 x 500Ω

5.5

12

0.012 x 500Ω

6

13

0.013 x 500Ω

6.5

14

0.014 x 500Ω

7

15

0.015 x 500Ω

7.5

16

0.016 x 500Ω

8

17

0.017 x 500Ω

8.5

18

0.018 x 500Ω

9

19

0.019 X 500Ω

9.5

20

0.020 x 500Ω

10

Converting mA to Voltage Signals